Some of the features of the new version are listed below:
1. Protection relays in accordance with IEC 60255
Over-current and Earth fault protection relays are now included in the devices list. The device can be used for Over-current and Earth fault protection with available settings for each case
2. Power factor panel
For each power factor correction unit you can create its power factor correction panel. This allows you to specify the capacitor bank steps used and the protective devices for each capacitor bank.
Click the image below to see a video that demonstrates this functionality:
3. New cables included
In this version we have included extra cables based on users' requirements.
3.1 Irish standard twin-earth cable
To comply with a new amendment of the Irish National Rules for Electrical Installations (ET101:2008, amendment 2.2) all new installations must use an insulated earth conductor that is the same size as the two phase conductors.
3.2 Aluminum Waveform and Concentric cables to BS7870
4. New circuit schedules report with Incomers
We have created a new report for circuit schedules with incomers.
5. Report Excel multi-page export
When exporting a report to excel it will now create a separate sheet per page.
6. Generator fault level calculations include the zero sequence reactance
When using a generator as the main source you can specify the zero sequence reactance percentage which will be included during the fault level calculations.
7. UPS internal impedance contributing to the fault current
UPS will also be contributing to the fault current when there is fault on UPS battery. This will be considered during the fault level calculations when the user sets the internal impedance of the UPS.
8. Protective Devices
8.1 Schneider:
RCCB acti9
MCCBs EasyPact
MasterPact ACBs NT
8.2 Hager
MCBs: MCN,MBN, HMC, HMD, HMF