Design Current and Calculation of the Minimum Required Value of the Cable's Current Carrying Capacity



General



For ring socket circuit with Ιn = 30Α or 32Α



Ring socket circuits otherwise


Grouped circuits not liable to
simultaneous overload



General motor circuits


Star-Delta Motor Circuits



With:


the design current of the circuit under consideration in Amperes

the nominal current or current setting of the protective device protecting the circuit against overcurrent  in Amperes

the minimum required value of the cable’s current carrying capacity


Criteria for type gG fuses - Comply with the IEC Standard requirement I2 ≤ 1.45 Iz:

As per the IEC standard, the condition I2 ≤ 1.45 Iz must be taken into account, where I2 is the fusing (melting level) current, equal to k2 x In (k2 ranges from 1.6 to 1.9) depending on the particular fuse concerned.

In such a case an extra factor k3 = 1.31 for fuses with In < 16A , or k3 = 1.1 for fuses with In ≥ 16A is considered, in order that I2 ≤ 1.45 Iz will be valid if In ≤ Iz/k3.



Checks



With:

the design current of the circuit under consideration in Amperes

the nominal current or current setting of the protective device protecting the circuit against overcurrent  in Amperes


the minimum required value of the cable’s current carrying capacity

the value of current tabulated in cable tables

Correction factor for ambient temperature

Correction factor for thermal insulation

Correction factor for grouping

Correction factor for using BS3036

Correction factor for ground installations

Correction factor for underground installation depth

Correction factor for ground soil thermal resistivity

Correction factor for triple harmonic currents

Motor starter overload. By default