Design Current and Calculation of the Minimum Required Value of the Cable's Current Carrying Capacity

General

For ring socket circuit with Ιn = 30Α or 32Α

Ring socket circuits otherwise

Grouped circuits not liable to simultaneous overload

General motor circuits

Star-Delta Motor Circuits

With:


|
the design current of the circuit under consideration in Amperes
|

|
the nominal current or current setting of the protective device protecting the circuit against overcurrent in Amperes
|

|
the minimum required value of the cable’s current carrying capacity
|
Criteria for type gG fuses - Comply with the IEC Standard requirement I2 ≤ 1.45 Iz:
As per the IEC standard, the condition I2 ≤ 1.45 Iz must be taken into account, where I2 is the fusing (melting level) current, equal to k2 x In (k2 ranges from 1.6 to 1.9) depending on the particular fuse concerned.
In such a case an extra factor k3 = 1.31 for fuses with In < 16A , or k3 = 1.1 for fuses with In ≥ 16A is considered, in order that I2 ≤ 1.45 Iz will be valid if In ≤ Iz/k3.
|
Checks


With:

|
the design current of the circuit under consideration in Amperes
|

|
the nominal current or current setting of the protective device protecting the circuit against overcurrent in Amperes
|

|
the minimum required value of the cable’s current carrying capacity
|

|
the value of current tabulated in cable tables
|

|
Correction factor for ambient temperature
|

|
Correction factor for thermal insulation
|

|
Correction factor for grouping
|

|
Correction factor for using BS3036
|

|
Correction factor for ground installations
|

|
Correction factor for underground installation depth
|

|
Correction factor for ground soil thermal resistivity
|

|
Correction factor for triple harmonic currents
|

|
Motor starter overload. By default

|
|